Wuhan GDZX Power Equipment Co., Ltd sales@gdzxdl.com 86--17362949750
Target Readers: Technical engineers, equipment selection personnel, and professionals who need to understand method principles and standard basis.
Cable fault testing involves three tiers of standards: equipment manufacturing standards, on-site operation specifications, and acceptance test standards, forming a complete standard system.
| Standard No. | Content | Status |
|---|---|---|
| DL/T 849.1-2019 | General Technical Conditions for Special Testing Instruments of Power Equipment Part 1: Cable Fault Flash Tester | Valid, implemented in May 2020, replacing the 2004 version |
| DL/T 849.2 | General Technical Conditions for Special Testing Instruments of Power Equipment Part 2: Cable Fault Locator | Valid |
| DL/T 849.3 | General Technical Conditions for Special Testing Instruments of Power Equipment Part 3: Cable Path Finder | Valid |
| DL/T 2530.2-2024 | General Technical Conditions for Power Cable Testing Equipment Part 2: Cable Sheath Fault Locator | Newly issued in 2024; specifies technical requirements for locators adopting step voltage method and pulsating rectangular wave current method |
| DL/T 846 Series | General Technical Conditions for High-Voltage Test Equipment | Reference for high-voltage generators |
| Standard No. | Content |
|---|---|
| DL/T 474-2018 | Guideline for Field Insulation Tests (including safety operation requirements) |
| DL/T 1919 | Guideline for Condition-based Maintenance of Overhead Lines, Cable Lines and Distribution Facilities in Distribution Network |
| Standard No. | Content |
|---|---|
| GB/T 50150-2016 | Standard for Electrical Equipment Handover Tests of Electrical Installation Engineering |
| IEC 60502 Series | Power Cables with Extruded Insulation and their Accessories for Rated Voltages from 1 kV to 30 kV (International Reference) |
| IEC 60840 | Test Methods for Cables with Rated Voltage above 30 kV (International Reference) |
Usage Tip: Standards are continuously updated. Please refer to the current valid version published on the official website of the Standardization Administration of China when citing.
Time Domain Reflectometry (TDR). A low-voltage narrow pulse is injected into the cable. The pulse propagates along the cable and reflects at positions with impedance mutation. The instrument calculates the fault distance by measuring the time difference.
Fault distance: S=V×Δt÷2
| Insulation Type | Reference Wave Velocity | Impact of Wave Velocity Deviation |
|---|---|---|
| Paper Insulated Lead Covered Cable (PILC) | ~160 m/μs | A 5% deviation causes a 50 m error for a 1000 m cable |
| Cross-linked Polyethylene (XLPE) | ~170 m/μs | Same as above |
| Ethylene Propylene Rubber (EPR) | 150-165 m/μs | Large differences among formulas; actual measurement is required |
| Fault Type | Transmitted Wave | Reflected Wave | Rule Summary |
|---|---|---|---|
| Open Circuit / Broken Cable | Positive | Positive | Same polarity for open circuit |
| Low-resistance Short Circuit (R ≤ 100 Ω) | Positive | Negative | Opposite polarity for short circuit |
| Pure Short Circuit (Impulse Flash Method) | Positive | Positive | Same as open circuit |
Distance per sampling point: S=V÷(2×f)
✅ Open circuit / broken cable faults
✅ Low-resistance short circuit ((R ≤ 100) Ω)
✅ Measure total cable length (for wave velocity calibration)
✅ Locate cable joints, T-joints and branch points
High-resistance faults maintain high impedance under low voltage, so low-voltage pulses cannot generate effective reflection. The impulse flash method applies high-voltage impulse to break down the fault point into an instantaneous electric arc (short-circuit state, lasting for tens of milliseconds). The traveling wave of pulse current is collected at this moment to obtain a clear reflected waveform similar to low-resistance short circuit.
220 V Mains → Voltage Regulator → High-Voltage Transformer → Energy Storage Capacitor → Discharge Gap → Fault Cable
Current Sampler → Test Host (Waveform Acquisition)
Key waveform features: Transmitted pulse, reflected pulse and negative reverse impulse.
For individual high-resistance faults, the impulse voltage passes through the fault point to the cable terminal, and flashover is triggered after voltage superposition during the return trip. The waveform presents a two-section structure.
Reading rule: Take the distance of the second section as the actual fault distance.
| Step | Operation |
|---|---|
| Step 1 | Appropriately widen the discharge gap to increase the threshold of impulse voltage |
| Step 2 | Increase the capacity of energy storage capacitor to boost single impulse energy |
| Step 3 | Apply continuous impulse for a long time to force the fault point to form a stable discharge channel |
✅ High-resistance leakage faults ((R > 100) Ω)
✅ High-resistance flashover faults
✅ Wet joint faults
✅ Faults causing tripping during operation with unobvious symptoms in low-voltage tests
A combination of low-voltage pulse method (high accuracy but invalid for high-resistance faults) and impulse flash method (applicable to high-resistance faults but complex waveforms):
This method uses clear waveforms of low-voltage pulse to realize positioning of high-resistance faults.
| Comparison Item | Pulse Current Method (Impulse Flash) | Secondary Pulse Method |
|---|---|---|
| Waveform Clarity | Disturbed by negative reverse impulse; interpretation requires experience | Similar to low-voltage pulse, intuitive to read |
| Applicable Faults | High-resistance leakage / flashover faults | High-resistance leakage faults (preferred) |
| Ranging Accuracy | Medium | Relatively high |
| Operation Difficulty | Need to identify negative reverse impulse | Relatively easy |
| Equipment Requirement | High-voltage equipment | High-voltage equipment + higher synchronization requirement |
✅ High-resistance leakage faults (higher accuracy than impulse flash method)
✅ Operators with insufficient experience (easy waveform interpretation)
✅ Scenarios requiring reliable ranging results
Note: This is a positioning method, not a ranging method. It is used for precise ground positioning after rough ranging.
Apply high-voltage impulse to the fault cable. Discharge at the fault point generates two signals:
Ground sensors receive both signals simultaneously. When the sensor is directly above the fault point, the propagation path difference between acoustic and electromagnetic signals is the smallest, and the time difference approaches zero.
Positioning Rule: Move the sensor to find the position with the minimum time difference (close to 0).
| Interference Source | Impact | Solution |
|---|---|---|
| Ground pipelines | Sound propagates along pipelines and forms false maximum values | Judge by time difference instead of sound volume only |
| Joint wells & manhole covers | Sound propagation path changes in cavities | Attach sensor closely to the ground and stay away from manhole covers |
| Closed faults (sheath faults) | Extremely weak discharge sound | Increase impulse voltage or adopt professional sheath positioning methods |
| Road noise | Background noise masks discharge sound | Avoid rush hours and turn on noise reduction mode |
| Fault Type | Applicability | Reason |
|---|---|---|
| High-resistance leakage / flashover faults | ✅ Most applicable | Obvious discharge sound |
| Low-resistance short circuit | ❌ Not applicable | No discharge sound; adopt audio induction method instead |
| Single-core sheath faults (closed type) | ⚌ Difficult | Extremely weak sound in sealed structure |
The loop of single-core high-voltage cable sheath fault consists of metal sheath, fault point and earth. Pulse signals attenuate severely due to the high attenuation coefficient of earth, so conventional pulse methods have an extremely limited effective ranging range and cannot realize effective positioning.
Based on Wheatstone bridge principle, calculate fault distance by measuring the resistance ratio between the faulty phase and healthy phase (or auxiliary wire). This method does not rely on pulse reflection and is immune to earth attenuation.
Apply DC or pulsating signal between sheath and earth, and measure the potential difference (step voltage) between two adjacent points on the ground. Abnormal change of step voltage near the damaged sheath indicates the direction and position of the fault point.
DL/T 2530.2-2024 General Technical Conditions for Power Cable Testing Equipment Part 2: Cable Sheath Fault Locator, newly issued in 2024, specifies technical requirements, test methods and inspection rules for locators adopting step voltage method and pulsating rectangular wave current method.
Sheath faults are usually closed faults with extremely weak discharge sound, so acoustic-magnetic synchronous method has poor effect. Professional sheath fault locators are required, and high operational experience is needed.
| Fault Type | Recommended Ranging Method | Recommended Positioning Method |
|---|---|---|
| Open circuit / Broken cable | Low-voltage pulse method | Acoustic detection method / Audio induction method |
| Low-resistance short circuit (≤100 Ω) | Low-voltage pulse method (priority for accuracy) | Audio induction method / Acoustic detection method |
| High-resistance leakage (>100 Ω) | Secondary pulse method (preferred) / Impulse flash method (alternative) | Acoustic-magnetic synchronous positioning method |
| Flashover faults | Direct flash method (if conditions permit) / Impulse flash method (after conversion) | Acoustic-magnetic synchronous positioning method |
| Sheath faults | Bridge method | Step voltage method |
Notes: All cited standards are valid versions at the time of compilation. Verify the current status of standards before use. Strictly comply with DL/T 474-2018 and relevant safety regulations during high-voltage tests.